CURRENT TRANSFORMER


Description
CURRENT TRANSFORMER 50/100:5A
Type SEC-15, CT Single phase, Outdoor Use, 60Hz
Maximum Voltage (U. Max.) ; 15.5kV
Primary Current (Ip) : 50 x 100A (Tap on the Primary Terminal)
Secondary Current (Is) : 5A (1 secondary winding)
CURRENT TRANSFORMER 150/100:5A
Type SEC-15, CT Single phase, Outdoor Use, 60Hz
Maximum Voltage (U. Max.) ; 15.5kV
Primary Current (Ip) : 150 x 300A (Tap on the Primary Terminal)
Secondary Current (Is) : 5A (1 secondary winding)
CURRENT TRANSFORMER 5/10:5A
Type SEC-15, CT Single phase, Outdoor Use, 60Hz
Maximum Voltage (U. Max.) ; 15.5kV
Primary Current (Ip) : 5 x 10A (Tap on the Primary Terminal)
Secondary Current (Is) : 5A (1 secondary winding)
CURRENT TRANSFORMER 15/30:5A
Type SEC-15, CT Single phase, Outdoor Use, 60Hz
Maximum Voltage (U. Max.) ; 15.5kV
Primary Current (Ip) : 15 x 30A (Tap on the Primary Terminal)
Secondary Current (Is) : 5A (1 secondary winding)
General Specifications:
Accuracy Class: 0.3 B0.9 thru B1.8 Full B0.9 tap (45VA)
Thermal Factor (Rated Voltage Factor) (Ft): 1.5 x In
Short time Thermal Current (Ith) : 80 x In - eff. 1second
Short time Dynamic Current (Idyn): 200 x In - Cr.
NI: 34/110/ -- (kV), BIL : 110kV
Insulation Material: Dry type Insulation (Cycloaliphatic Epoxy Resin)
Standard: ANSI C57.13/93
Insulation Class / Temperature Rise: Class "A" (1050C)
 
 
 